ANALOG I/O CHAPTER 8
8-2
Initializing Inputs
The RPC-2350 can have up to eight single-ended inputs,
four differential, or a mixture of single ended and
differential inputs. On a reset, inputs are configured for
0-5V, single ended.
Initialization is performed using the CON FIG AIN
command. T he syntax is:
CONFIG AIN channel, input, range
Where:
channel is from 0 to 7 for single-ended or
differential. Differential inputs require 2 lines and
are specially paired as shown below. The channels
you specify in a "mixed" application depends upon
what lines ar e used for single ended and differential.
Differential inputs operate in a special way. Use the
following two tables for differ ential inputs.
When channe l = odd
Ch # 0 1 2 3 4 5 6 7
Polarity - + - + - + - +
channel 1 1 3 3 5 5 7 7
J7 pin # 1 3 5 7 9 11 13 15
When channe l = even
Ch # 0 1 2 3 4 5 6 7
Polarity + - + - + - + -
channel 0 0 2 2 4 4 6 6
J7 pin # 1 3 5 7 9 11 13 15
For example, if you wanted one differential input,
channel 0 would use J7 pin nu mber s 1 and 3. Single
ended inputs 2-7 are available.
input specifies single ended or differential. 0 =
differential, 1 = single ended.
range is voltage input. 0 = ±2.5V and 1 = 0 to
+ 5V.
Differential Mode
When differential m ode is specified, inputs are actually
pseudo-differential. What this means is that a ground
reference is needed. For example, you cannot place a
battery between channel 0 and 1 and get an ac curate
reading. The (-) input must be referenced to ground.
An example of where pseudo-differential works is an
output from a bridge network.
A pseudo-differential input subtracts the DC component
from an input. The IC maker recomm ends the (-) input
remain stable within 1 count with respect to ground for
best results. Connecting a 0.1 uF capacitor from the (-)
input to ground works well.
When operating in differential mode, relative + and -
voltages must be connected to specific inputs. When
inputs are reversed, a conversion returns a 0. When the
relative voltage changes, perform a conversion on the
alternate channel. CONFIG AIN must be perfor med on
both channels to be valid.
Pairs of channels c an be differ ential while others single
ended. Thus, if channel 0 and 1 are differ ential inputs,
channels 2-7 may be single ended.
Examples u sing CON FIG AIN
Below are sample syntaxes for the CON FIG AIN
command:
1. Single ended mode, 0-5V input
CONFIG AIN chan,1,1
The input voltage is from 0 to 5 volts. The result from
the AIN function is 0 for 0.000V and 4095 for
+ 4.9988V. chan may range from 0 to 7, if no other
channels are used for differential inputs.
2. Differential mode, 0 to + 5V input
CONFIG AIN chan,0,1
chan can be 0, 2, 4, or 6. The input may range from 0
to + 5V. However, if the (-) input is more positive than
the (+ ) input, the result w ill always be zero. The result
from the AIN function is 0 for a difference of 0.000V
and 4095 for a difference of 4.9988V.
3. Single ended, ±2.5V input
CONFIG AIN chan,1,0